Quality AC DC Mixed IT System Insulation Monitoring Device with Low Frequency Pulse Injection and IEC61557-8 Compliance Insulation Monitor factory
<
Quality AC DC Mixed IT System Insulation Monitoring Device with Low Frequency Pulse Injection and IEC61557-8 Compliance Insulation Monitor factory
>

AC DC Mixed IT System Insulation Monitoring Device with Low Frequency Pulse Injection and IEC61557-8 Compliance Insulation Monitor

Brand Name: Sikcon
Model Number: SKIM800E
Place of Origin: China
Minimum Order Quantity: 50 Sets
Price: 120$-150$
Supply Ability: 10000pcs/month

Product Details


Power Supply: AC 115V-265V 50/60Hz DC 110V-220V Product Name: Economical Insulation Monitoring Device
Alarm Threshold: 1kΩ -99K Measuring Current: ≤80μA

Product Description

🔎 Overview

The SKIM200E is a DIN-rail insulation monitor designed for ungrounded IT power systems, widely deployed in industrial control panels, energy storage and DC cabinet applications across Europe and Southeast Asia.

Adopting low-frequency pulse square wave injection technology, it continuously measures the insulation resistance to earth of the monitored network. It enables early detection of insulation ageing, cable damage and moisture degradation, preventing touch-voltage hazards, short circuits and unexpected production shutdowns.

⚠️ Important Notice This unit supports AC, DC and mixed AC/DC IT systems. It monitors total bus insulation only and does NOT support branch fault location.

Designed in compliance with IEC 61557-8.

📐 Model Selection Guide SKIM200E is the standard model for overall busbar insulation supervision, without branch fault tracing function. 💡 Send us your system voltage and site specifications, our engineers will verify compatibility before order placement.

✨ Key Features

⚡ Universal Monitoring for AC / DC / Mixed AC-DC IT Systems Low-frequency pulse injection method provides stable readings even with high stray capacitance from long cables, inverters and energy storage loops. It effectively suppresses false alarms caused by capacitive leakage current. 📟 Threshold Setting via Front Encoder Alarm threshold adjustable from 1kΩ to 99kΩ directly on the front panel encoder. No PC software or upper computer required; simple commissioning for local technicians. 🔄 Built-in Self‑Test & Inhibit Function Integrated self-test simulates insulation faults to verify measurement channel and relay operation, ideal for annual inspection and site acceptance without extra test instruments. The enable/inhibit function temporarily disables monitoring during maintenance and high-voltage withstand tests to avoid false triggering. 🔌 Wide Control Supply & Low Power Consumption Control supply: AC 115–265V (50/60Hz) / DC 110–220V, compatible with most industrial cabinet power supplies. Rated power ≤2W for energy-saving continuous operation. 📡 Dual Independent Relay Output for Graded Protection Two separate relay groups for pre-alarm and fault alarm: 1 NO pre-alarm contact (250V/6A) for beacon lights or buzzers; 1 changeover relay (NO+NC, 250V/3A) for safety interlock and machine shutdown. Graded alarm logic avoids unnecessary production stops. 🛡 Compact Industrial DIN-Rail Design 36mm narrow housing, dimension 96×36×70mm, standard 35mm DIN rail mounting for compact cabinet layout. Operating temperature range -20℃ ~ +55℃, suitable for hot and humid industrial cabinets.

📋 Technical Specifications

Item Specification
Applicable System Ungrounded IT system, AC / DC / mixed AC-DC
Measuring Principle Low-frequency pulse square wave injection
Measuring Range 1kΩ–999kΩ
Alarm Threshold 1kΩ–99kΩ, adjustable via front encoder
Measuring Pulse 24V pulse, measuring current ≤80μA
Internal Impedance 600kΩ for DC / 600kΩ for AC
Control Supply AC 115–265V (50/60Hz) / DC 110–220V
Power Consumption ≤2W
Alarm Output Pre-alarm: 1×NO 250V/6A; Fault alarm: 1×changeover (NO+NC) 250V/3A
Additional Functions Built-in self-test, monitoring inhibit function
Mounting 35mm DIN rail
Dimension 96×36×70mm
Net Weight ≤180g
Operating Temperature -20℃ ~ +55℃
Relative Humidity <95%
Remark Total insulation monitoring only; no branch fault location; Made in China

🏭 Typical Applications

  • Machine tool control panels
  • Inverter drive cabinets
  • DC panels and DC bus control circuits
  • Energy storage systems & charging equipment control cabinets
  • Isolated industrial power supply cabinets
  • Electrical test and commissioning benches

❓ FAQ

Q: What power systems can SKIM200E be used for?

A: It is suitable for ungrounded IT systems, supporting AC, DC and mixed AC/DC circuits. Online monitoring max. Un ≤ AC300V / DC300V; offline pre-test up to AC690V / DC690V. It monitors overall bus insulation and cannot locate individual faulty branches.

Q: Will it trigger frequent false alarms for inverter cabinets with large bus capacitance?

A: The low-frequency pulse injection design resists capacitive leakage interference. Readings remain stable under fluctuating bus capacitance, which is perfect for inverters and energy storage loops.

Q: Is it easy to adjust the alarm setpoint?

A: The threshold is set directly by the front encoder from 1kΩ–99kΩ. Settings take effect immediately without host software.

Q: Will false alarms occur during maintenance or HV withstand tests?

A: The built-in inhibit function allows temporary monitoring suspension during maintenance and high-voltage testing to prevent false alarms.

Q: Can it connect to buzzers, warning lights or PLC interlock?

A: Yes. Pre-alarm contact drives sound & light beacons; the changeover fault relay can be wired to PLC digital inputs or safety shutdown interlock circuits.

Q: What are the power supply requirements?

A: Separate control supply required: AC115–265V or DC110–220V, power consumption ≤2W.

Q: What is the warranty period and can you issue commercial invoices?

A: 18 months factory warranty, commercial invoice available.

📦 Package & Warranty

In the Box 1 × SKIM200E Insulation Monitor 1 × English user manual ⚠️ Signal cables, warning beacons and current transformers are NOT included, available on separate quotation.

Warranty 18-month factory warranty against manufacturing defects Exclusions: damage caused by moisture ingress, dust, over-temperature, lightning strike, unauthorized disassembly/modification and wrong wiring Support: free English datasheet, wiring diagram and online technical guidance; on-site service not covered.

🛒 Purchase Information

  • ✅ Fast shipment for stock items; bulk order lead time available upon request
  • ✅ Commercial invoice provided
  • ✅ Confirm system voltage and working conditions before ordering for compatibility check
  • ✅ Submit single-line diagram and site conditions for free technical review
  • ✅ Customization requests welcome, contact us for evaluation

Product Highlights

SKIM200E DIN-rail insulation monitor for AC/DC/mixed IT systems. Low-frequency pulse injection resists high stray capacitance, avoiding false alarms. Front encoder sets 1kΩ-99kΩ threshold; dual relays enable graded alarms. IEC 61557-8 compliant, ≤2W, built-in self-test/inhibit. 18-month warranty, OEM customization available.

Related Products
Quality AC DC Mixed IT System Insulation Monitoring Device with Low Frequency Pulse Injection and IEC61557-8 Compliance Insulation Monitor factory

AC DC Mixed IT System Insulation Monitoring Device with Low Frequency Pulse Injection and IEC61557-8 Compliance Insulation Monitor

SKIM200E DIN-rail insulation monitor for AC/DC/mixed IT systems. Low-frequency pulse injection resists high stray capacitance, avoiding false alarms. Front encoder sets 1kΩ-99kΩ threshold; dual relays enable graded alarms. IEC 61557-8 compliant, ≤2W, built-in self-test/inhibit. 18-month warranty, OEM customization available.

Quality SKIM200E DIN Rail Insulation Monitor for AC DC Mixed IT System, Low-Frequency Pulse Injection, 1k–999kΩ factory

SKIM200E DIN Rail Insulation Monitor for AC DC Mixed IT System, Low-Frequency Pulse Injection, 1k–999kΩ

SKIM200E DIN-rail insulation monitor for AC/DC/mixed IT systems. Low-frequency pulse injection resists high stray capacitance, avoiding false alarms. Front encoder sets 1kΩ-99kΩ threshold; dual relays enable graded alarms. IEC 61557-8 compliant, ≤2W, built-in self-test/inhibit. 18-month warranty, OEM customization available.

Quality Tropical Factory Insulation Monitoring Device with Wide Voltage Tolerant and Anti Nuisance Alarm for IT Systems factory

Tropical Factory Insulation Monitoring Device with Wide Voltage Tolerant and Anti Nuisance Alarm for IT Systems

The SKIM600M is a tropical-ready IT insulation monitor for AC690V/DC400V systems, featuring low-frequency injection for stable measurement, wide voltage tolerance, Modbus RS485, and adjustable alarm delay to suppress nuisance alarms. Ideal for palm oil mills and humid industrial sites.

Quality Insulation Monitoring Device with Simultaneous Insulation Resistance and Leakage Capacitance Measurement, Modbus RS-485 Communication and DIN Rail Mounting for IT Systems factory

Insulation Monitoring Device with Simultaneous Insulation Resistance and Leakage Capacitance Measurement, Modbus RS-485 Communication and DIN Rail Mounting for IT Systems

The SKIM600M is an IEC 61557-8:2015-certified insulation monitoring device for IT systems up to AC 690 V/DC 400 V. It simultaneously measures insulation resistance and leakage capacitance (<4.5mA) using low-frequency injection without disturbing operation. Features include Modbus RS-485, dual alarm relays, backlit LCD, and DIN rail mounting for reliable, efficient busbar supervision.

Request A Quote

Please use our online inquiry contact form below if you have any questions, our team will get back to you as soon as possible.

You can upload up to 5 files and Each file sized 10M max.